中文

English


CATEGORY
OLT
ONU
PON Module
Optical Transceiver
交换机
路由器
DSLAM/MDU
Power Supply
仪器
网络配件
思科连接线
Speakers & Accessories



Contact Us  
TEL:+86 755 23225716
FAX:+86 755 23209516
EMAIL:info@hkyouzi.com
Skype:hkyouzi
ADD:Room303,HongJunXinYe Building, FanShenDaDao, BaoAn District,ShenZhen, GuangDong,China



ZTE_ZXDU48 B600_ power system
Name: power system
Model: ZXDU48 B600
Manufacturer: ZTE
Producing Area: CN
Simple Description: ZXDU48 B600 power system with 1xCSU520Y 2xZXD1500
Price: Inquire   hot sale
Overview

1U height, can be installed in a 19-inch rack

ZXDU48 B600, 3 LOAD, 1 BATT

Supports 220V single-live wire voltage input and 110V dual-live wire input

Operates in the phase-to-neutral voltage range from 85V to 295V

Operates in the AC range from 45Hz to 66Hz

The rated DC output voltage is -53.5V and continuously adjustable from -42V to -58V

Provides input/output dry contacts and RS232 ports

ZXDU48 B600 is 1U (height) x 19-inch (width) embedded DC power system that can supply power to -48V series communication devices. Comprises a PDU unit, a CSU and ZXD1500 rectifiers.

ZXDU48 B600 power system complies with the RoHS (2002/95/EC) requirements in the European Union.

Tech Specs
Specification
Item Description

Operating temperature

-33℃ to +55℃

Sheds the load when they system operates in a temperature higher than 55℃

Powers off automatically when the system temperature is higher than 75℃

Storage temperature

-45℃ to +70℃

Relative humidity

5% to 95% (non-condensing). It is recommended that the relative humidity is in the range of 40% to 60%

Altitude

0m to 2000m: Outputs in full power

2000m to 3000m: Derated by 1% for every 100m increase of altitude

Space requirementThe system must be installed in a 19-inch cabinet or rack.

The system must be horizontally installed. The cabinet must be definitely vertical. No bump is allowed.

There should be no liquid or conductive objects within, or dropping into the cabinet.

The system must not be installed near any water, corrosive gas, or explosive materials.

There should be no conductive dust or electromagnetic interference in the vicinity.

System capacity3200W/66A. Two ZXD1500 rectifiers are required for full configuration
System efficiencyPeak efficiency: 95%

Power limitation based on the input voltage

AC input ≤85 V± 5 V

The output power of the rectifier is 0%.

AC input (85 V±5 V) to 110 V

The power drops linearly. The output power of the rectifier ranges from 40% to 60% of the overall power.

AC input 110 V to 176 V

The power drops linearly. The output power of the rectifier ranges from 60% to 100% of the overall power.

AC input 176 V to (305 V±5 V)

The output power of the rectifier is 100%.

AC input >305 V±5 V

The output power of the rectifier is 0%.

Power limitation based on the temperature

Ambient temperature: -33℃ to +55℃The output power of the rectifier is 100%
Ambient temperature: +55℃ to +75℃ The output power decreases linearly as the temperature rises. When the environmental temperature reaches 70°C, the output power is no lower than 62.6% of the maximum power.
Ambient temperature: >+75°C The output power of the rectifier is 0% (power-off protection)
Over all noise (sound pressure)≤68 dB(A)
Network architecture for monitoringRS232 ports connected in series
Mean time between failuresMTBF≥3.2x 10⁵ h
Design life 10 years to 15 years
Input AC featuresAC input mode Three-wire single-phase system (LN/PE). Compatible with dual-live wires (L1/L2/PE)
Input AC voltageRated phase-to-neutral voltage: 200 V to 240 V

Range of phase-to-neutral voltage: 85 V to 295 V

Input frequencyRated frequency: 50 Hz/60 Hz

Frequency range: 45 Hz to 66Hz

Input PFThe PF is no lower than 0.996 at the rated load.
Total harmonic distortion THD≤5% when the system operates at a power ranging from 30% to 100% of the rated power.
AC lightning protection A lightning protection module is embedded in the rectifier.
AC power distribution Number of AC inputs 1
AC input circuit breaker 3xrimping terminals
Stanby AC output -
Protection featureAC overvoltage protection The overvoltage protection takes effect when the single-phase input voltage is higher than the AC overvoltage protection threshold.
AC undervoltage protection The undervoltage protection takes effect when the single-phase input voltage is lower than the AC under voltage protection threshold.
Output DC propertiesRated DC output voltage -53.5 V DC
Range of the DC output voltage Continuously adjustable from -41 V to -58 V (adjust by the CSU)
Voltage drop in the cabinet ≤500 mV

Regulated voltage precision

≤0.6%

Psophometrically weighted noise voltage

≤2 mV

DC lightning

Maximum current of the lightning arrester: Imax = 3 kA (8/20 μs)

DC power distribution

Battery inputs

One input. 1 x 30 A, configured with a 40 A fusible link

Protection feature

Power-off protection mode

Battery Low Voltage Disconnect (BLVD)

DC load outputs

Two outputs. 2 x 20 A, configured with a 40 A fusible link

DC overvoltage protection

The overvoltage protection takes effect when the output voltage is higher than the DC overvoltage protection threshold.

DC undervoltage protection

The undervoltage protection takes effect when the output voltage is lower than the DC overvoltage protection threshold.

Battery undervoltage protection

The power-off protection takes effect when the battery voltage is lower than the power -off voltage protection threshold.

Dimensions

1U height / 19-inch width

43.6 mm x 482.6 mm x 260 mm (Height x Width x Depth)

Overall weight (including the rectifiers)

Around 8 kg

Installation mode

Embedded in a 19-inch cabinet

zxdu48 B600_03


zxdu48 B600_02


zxdu48 B600_01

Back


Copyright ©2005-2024  心和电子   All rights reserved     
Tel:86 755 23225716  Fax:86 755 23209516  Email:info@hkyouzi.com